Zusammenfassung

Long-wave oscillations of stranded conductors occur on high-voltage overhead lines under certain circumstances. The approach of the main conductors may result in a considerable impairment of the electric power transmission. The application of phase spacers. so-called separators, makes it possible to prevent such oscillations of stranded conductors. or to manage them. The work carried out in the GDR in view of development and construction as well as the beneficial experience regarding the application and the effect of separators of porcelain long-rod insulators is reported on.