Great importance is attached to the problem of wind-induced vibrations and the danger they present to high-voltage
overhead conductors. This report deals with the results of vibration tests performed while the line was in operation. Comparison
measurements were made on ACSR conductors with various tensile stresses and conductor types. The influence
of bundled conductors, vibration dampers and special arrangements of the suspension point were also investigated. In addition
to tlze vibration measurements, the static bending stress at the suspension clamp was also measured.
While at the beginning of our tests conductor vibrations were considered the main problem. as they used to be in
the past. the measurements obtained made us realize that dynamic and static bending stresses at the suspension clamp
have to be considered together with the tensile stress and that the static bending stress at the suspension clamp is an
important factor which has so far been ignored.
%0 Generic
%1 buckner1968stresses
%A BUCKNER, W
%A KERNER, H
%A PHILIPPS, W
%D 1968
%K Clamp Conductor Line Stress Suspension Transmission
%T STRESSES IN TRANSMISSION LINE CONDUCTORS NEAR THE SUSPENSION CLAMP
%X Great importance is attached to the problem of wind-induced vibrations and the danger they present to high-voltage
overhead conductors. This report deals with the results of vibration tests performed while the line was in operation. Comparison
measurements were made on ACSR conductors with various tensile stresses and conductor types. The influence
of bundled conductors, vibration dampers and special arrangements of the suspension point were also investigated. In addition
to tlze vibration measurements, the static bending stress at the suspension clamp was also measured.
While at the beginning of our tests conductor vibrations were considered the main problem. as they used to be in
the past. the measurements obtained made us realize that dynamic and static bending stresses at the suspension clamp
have to be considered together with the tensile stress and that the static bending stress at the suspension clamp is an
important factor which has so far been ignored.
@conference{buckner1968stresses,
abstract = {Great importance is attached to the problem of wind-induced vibrations and the danger they present to high-voltage
overhead conductors. This report deals with the results of vibration tests performed while the line was in operation. Comparison
measurements were made on ACSR conductors with various tensile stresses and conductor types. The influence
of bundled conductors, vibration dampers and special arrangements of the suspension point were also investigated. In addition
to tlze vibration measurements, the static bending stress at the suspension clamp was also measured.
While at the beginning of our tests conductor vibrations were considered the main problem. as they used to be in
the past. the measurements obtained made us realize that dynamic and static bending stresses at the suspension clamp
have to be considered together with the tensile stress and that the static bending stress at the suspension clamp is an
important factor which has so far been ignored.},
added-at = {2020-05-04T01:11:39.000+0200},
author = {BUCKNER, W and KERNER, H and PHILIPPS, W},
biburl = {https://www.bibsonomy.org/bibtex/2b7e3e8fc52ca85481aac3b2ac337b1fc/ceps},
interhash = {c4c2199f4985769d0425d0819040f2e7},
intrahash = {b7e3e8fc52ca85481aac3b2ac337b1fc},
keywords = {Clamp Conductor Line Stress Suspension Transmission},
timestamp = {2023-12-21T14:59:26.000+0100},
title = {STRESSES IN TRANSMISSION LINE CONDUCTORS NEAR THE SUSPENSION CLAMP},
year = 1968
}