ELECTRIC PERFORMANCE OF NONCERAMIC PHASE-TO-PHASE SPACERS FOR 275KV TRANSMISSION LINES

, , , , and .
(1993)

Abstract

Ceramic phase-to-phase spacers have been employed to prevent gal loping on 275kV overhead transmission lines since 1989 in Hokkaido Electric Power Co., Inc. After these phase-to-phase spacers were attached, phase-short circuit due to galloping have not taken place. But the weight of this spacer is heavy because the ceramic long rod is used as a insulator. This heaviness it makes problems that the height of conductor from ground can not be gained to safety level in case of thin conductors, reinforcement of Tower angle parts increases and so on. To cope with those, we developed phase-to- phase spacer with nonceramic insulator instead of of ceramic one so that we can reduce the weight of phase-to-phase spacer. Through tests on its fundamental performance which are mechanical and electrical strength, it was proved that nonceramic phase-to-phase spacer reached a practical level. The developed spacers were attached on 275kV transmission lines with double conductors, only 1 span, in 1992. And the observation has been done to size up the efects of those spacers. This report mainly describes the results of electric performance test including condition of icing.