ELECTRIC PEKFORMANCE OF NONCERAMIC PHASE-TO-PHASE SPACERS FOR 275KV TRANSMISSION LINES

, , , , and .
(-)

Abstract

Ceramic phase-to-phase spacers have been e1plo¥ed to prevent galloping on 275kV overhead trans•ission lines since 1989 In Hokkaido Electric Power Co., Inc. After these phase-to-phase spacers were attached, phase-short circuit due to galloping have not taken place. But the weight of this spacer is heavf because the cera1ic long rod is used as a insulator. This heaviness it 1akes proble1s that the height of conductor from ground can not be gained to safet¥ level In case of thin conductors, reinforcement of Tower angle parts increases and so on. To cope with those, we developed phase-to-Phase spacer with nonceramic insulator Instead of of ceramic one so that we can reduce the weight of phase-to-phase spacer. Through tests on its funda1ental performance which are aechanical and electrical strength, It was proved th>l.t nonceramlc phase-to-phase spacer reached a practical level. The developed spacers were attached on 275kV transmission lines with double conductors, only I span, in 1992. And the observation has been done to size up the efects of those spacers. This report 1ainl¥ describes the results of electric perforaance test Including condition of Icing.